1. Вступ
This manual provides detailed instructions for the installation, operation, and maintenance of the Elitech CP-6000N Current Monitoring Relay. The CP-6000N is designed for comprehensive electrical system protection, offering current monitoring, overload protection, phase monitoring, and temperature control capabilities with RS-485 communication.
2. Інформація про безпеку
Please read all safety instructions carefully before installation and operation. Failure to follow these instructions may result in equipment damage, personal injury, or death. Only qualified personnel should perform installation and maintenance.
- Disconnect all power sources before wiring or servicing the device.
- Забезпечте належне заземлення, щоб уникнути ураження електричним струмом.
- Verify all connections are secure and correct according to the wiring diagram.
- Do not operate the device in environments exceeding its specified operating conditions.
3. Продукт закінчивсяview
The Elitech CP-6000N is an advanced current monitoring relay offering robust protection features for industrial and commercial applications. It integrates new phase sequence detection, phase loss protection, unbalance, and overload protection. With a three-phase current detection capability up to 200A and RS-485 communication, it allows for real-time remote monitoring.

Малюнок 1: Спереду view of the Elitech CP-6000N Current Monitoring Relay, showing the digital display and control buttons.

Figure 2: Icons representing key features of the CP-6000N, including phase sequence, phase loss, unbalance, overload protection, 220A maximum current, RS-485 communication, and alarm function.
4. особливості
- New phase sequence detection and protection design.
- Phase loss protection.
- Unbalance protection.
- Захист від перевантаження.
- Three-phase current detection, with over-current protection up to 200A.
- Higher measurement accuracy: up to ±2A (0-30A).
- RS-485 communication function for remote monitoring of compressor running status.
- Current measurement range: 2-80A; 30-200A.
5. Технічні характеристики
| Специфікація | Значення |
|---|---|
| Бренд | Елітех |
| Модель | CP-6000N-SP-220V |
| Тип монтажу | Кріплення DIN на рейці |
| Підсвічування | так |
| Тип роз'єму | Гвинт |
| Контактний матеріал | Срібло |
| Тип контакту | Нормально закритий |
| Поточний рейтинг | 200 Amps |
| Режим роботи | Автоматичний |
| Сертифікати | CE, UL |
| UPC | 781454242306 |
6. Налаштування та встановлення
6.1 Монтаж
The Elitech CP-6000N is designed for DIN Rail mounting. Ensure the DIN rail is securely installed in a suitable enclosure, providing adequate ventilation and protection from environmental factors.

Figure 3: Mounting dimensions of the CP-6000N, indicating a width of 2.8 inches and a height of 1.14 inches.
6.2 Схема підключення
Follow the wiring diagram carefully to ensure correct power supply, current sensor connections, and RS-485 communication. Incorrect wiring can lead to malfunction or damage.

Figure 4: Wiring diagram for the CP-6000N, showing terminals for Alarm, Power (W, V, U, N), Current Sensor (COM, A, B, C), and RS-485 (B-, A+).
Описи терміналів:
- 1-2: Alarm output contacts.
- 3-6 (W, V, U, N): Three-phase power input.
- 7 (COM): Common terminal for current sensors.
- 8-10 (A, B, C): Current sensor inputs for phases A, B, and C.
- 11-12 (B-, A+): RS-485 communication terminals.
7. Інструкція з експлуатації
7.1 Основна операція
The CP-6000N features a digital display and several buttons for configuration and monitoring.

Figure 5: A hand interacting with the control buttons of the CP-6000N, highlighting ease of use.
- Набір/View кнопка: Press to enter parameter setting mode or view різні параметри.
- Esc Button: Press to exit the current menu or cancel an operation.
- Стрілки вгору/вниз: Use to navigate through menu options or adjust parameter values.
7.2 Current Monitoring
The device continuously monitors the three-phase current. The current measurement range is 2-80A or 30-200A, depending on the specific model variant. The digital display shows the measured current values.
7.3 Зв'язок RS-485
The integrated RS-485 communication function allows the CP-6000N to be connected to a network for remote monitoring. This enables real-time tracking of compressor status and other operational data. Refer to the RS-485 communication protocol document for detailed integration instructions.
8. Технічне обслуговування
The Elitech CP-6000N is designed for reliable operation with minimal maintenance. However, periodic checks are recommended to ensure optimal performance and longevity.
- Візуальний огляд: Regularly inspect the device for any signs of physical damage, loose connections, or overheating.
- Прибирання: Тримайте пристрій чистим та без пилу та сміття. Використовуйте м’яку суху тканину для очищення. Не використовуйте рідкі засоби для чищення.
- Перевірки підключення: Periodically verify that all wiring connections are secure.
9. Вирішення проблем
If the CP-6000N exhibits unexpected behavior or displays fault codes, refer to the following information.

Figure 6: Table of fault codes and their meanings for the CP-6000N.
| немає | Код несправності | Значення |
|---|---|---|
| 1 | EPS | Помилка послідовності фаз |
| 2 | EPL | Захист від втрати фази |
| 3 | EoL | Захист від перевантаження |
| 4 | EUb | Захист від дисбалансу |
Загальні поради щодо усунення несправностей:
- Немає живлення: Check power supply connections and circuit breakers.
- Неправильні показання: Verify current sensor connections and calibration settings.
- Проблеми зв'язку: Check RS-485 wiring, baud rate, and address settings.
10. Гарантія та підтримка
Elitech products are manufactured to high-quality standards and are backed by a manufacturer's warranty. For specific warranty terms and conditions, please refer to the warranty card included with your product or visit the official Elitech webсайт.
For technical support, troubleshooting assistance, or service inquiries, please contact Elitech customer service through their official webабо контактну інформацію, надану під час покупки.