1. Вступ
The SmartGen HAT560NB ATS Controller is an intelligent dual-supply module designed for Automatic Transfer Systems (ATS). It integrates digital, intelligent, and networked functionalities to provide precise voltage measurement and control for various power supply configurations. This controller is suitable for specialized ATS, Contactor ATS, and Air Break ATS applications, offering a compact structure, advanced circuitry, and high reliability.
It is engineered to reduce operational errors through automatic measurement and control, making it an ideal solution for managing power transfer between different sources like mains and generators.

Малюнок 1: Спереду view of the SmartGen HAT560NB ATS Controller, showing the LCD display and operational buttons.
2. Features and Characteristics
The HAT560NB controller incorporates a powerful microprocessor for accurate monitoring and control. Key features include:
- System type configuration: Mains (1#) & Generator (2#), Generator (1#) & Mains (2#), Mains (1#) & Mains (2#), Generator (1#) & Generator (2#).
- 132x64 LCD with backlight, offering optional Chinese and English display with push-button operation.
- Measurement and display of 2-way 3-phase voltagе і частота.
- Захист від пере/зниження об'ємуtage, loss of phase, reverse phase sequence, and over/under frequency.
- Automatic and Manual operating modes. Manual mode allows forced switch closure or opening.
- All parameters are configurable on-site, secured by two different passwords for authorized access.
- Genset commissioning can be set to On-load or Off-load mode.
- Automatic re-closing function for the ATS Controller.
- Configurable closing output signal as either on intervals or continuous output.
- Applicable for ATS with one neutral position, two neutral positions, and non-position types.
- Monitors 1-3 phase AC mains voltagес.
- Manages changeover of both generator and mains contactors.
- Sends remote start commands to the generating set.
- Compatible with various contactors and changeover switch types.
3. Налаштування та встановлення
Proper installation is crucial for the safe and reliable operation of the HAT560NB controller. Ensure all power is disconnected before beginning installation. Refer to the wiring diagrams and terminal descriptions for correct connections.
3.1 Схеми підключення
The HAT560NB controller supports various wiring configurations depending on the ATS type. Below are typical wiring diagrams for different setups. Always consult a qualified electrician for installation.

Figure 2: Comprehensive wiring diagrams illustrating connections for ATYS3S, SGQ-N/T, SGQ-M, and VITZRO/PHETENG ATS controller types. These diagrams show connections for 1# and 2# power supplies, load, and remote start signals.

Figure 3: Additional wiring diagrams focusing on SGQ-N/T, SGQ-M, and Contactor ATS configurations, detailing input and output connections for the controller.
3.2 Підключення клем
The controller features clearly labeled terminals for power input, auxiliary outputs, and control signals. Ensure each wire is securely connected to its designated terminal.

Малюнок 4: Задня частина view of the HAT560NB controller, displaying the layout and labeling of all connecting terminals, including power inputs, auxiliary outputs, and communication ports.
4. Інструкція з експлуатації
The HAT560NB controller offers both automatic and manual operation modes, accessible via its front panel buttons and LCD display.
4.1 Увімкнення та початковий дисплей
Upon powering on, the LCD will display system information, including voltage and frequency readings for both power sources. The backlight ensures visibility in various lighting conditions.
4.2 Вибір режиму
- Автоматичний режим: The controller automatically monitors the power sources and initiates transfer based on pre-set parameters and detected abnormalities (e.g., over/under voltage, frequency deviations, phase loss).
- Ручний режим: Allows the user to manually control the opening or closing of the transfer switches. This mode is typically used for testing or specific operational requirements.
4.3 Налаштування параметрів
All operational parameters can be configured directly on the unit using the push-buttons and LCD interface. Access to parameter settings is protected by a two-level password system to prevent unauthorized changes. Refer to the detailed programming guide (not included in this manual) for specific parameter definitions and adjustment procedures.
5. Технічне обслуговування
Regular maintenance ensures the longevity and reliable performance of your HAT560NB ATS Controller.
- Прибирання: Keep the controller's exterior clean and free from dust and debris. Use a soft, dry cloth. Avoid abrasive cleaners or solvents.
- Перевірки підключення: Періодично перевіряйте всі з'єднання проводів, щоб переконатися в їх надійності та відсутності корозії. Нещільні з'єднання можуть призвести до перебоїв у роботі або збоїв системи.
- Умови навколишнього середовища: Забезпечте дотримання заданих температурних та вологісних норм у робочому середовищі, щоб запобігти пошкодженню внутрішніх компонентів.
Для будь-якого внутрішнього технічного обслуговування або ремонту зверніться до кваліфікованого сервісного персоналу.
6. Вирішення проблем
This section provides guidance on common issues you might encounter with the HAT560NB controller.
| проблема | Можлива причина | Рішення |
|---|---|---|
| Контролер не вмикається | No DC power supply; Incorrect wiring | Check DC 8.0V-35.0V power supply connections; Verify wiring according to diagrams. |
| ATS не переводиться автоматично | Automatic mode not selected; Fault detected on active power source (e.g., over/under voltage, frequency); Incorrect parameters | Ensure controller is in Automatic mode; Check power source status; Verify parameter settings. |
| Display shows error for voltagе/частота | Actual power source issue; Sensor/input wiring problem | Перевірте фактичний обсягtage and frequency of the power source; Inspect AC voltage вхідна проводка. |
| Кнопки не реагують | Тимчасовий збій програмного забезпечення; Проблема з обладнанням | Restart the controller by cycling power; If issue persists, contact support. |
7. Технічні характеристики
The following table details the technical specifications for the SmartGen HAT560NB ATS Controller.

Figure 5: Detailed specifications table for the HAT560N series ATS Controller, including operating voltage, power consumption, AC voltage input ranges, rated frequency, relay outputs, communication, dimensions, and environmental conditions.
| Пункт | Специфікація |
|---|---|
| Робочий випtage | DC 8.0V-35.0V (continuous power supply) |
| AC Voltage Вхід | AC170V-270V (during AC power L1N1/L2N2 supply) |
| Споживана потужність | <3 Вт (режим очікування: <2 Вт) |
| Номінальна частота | 50/60 Гц |
| Закрити релейний вихід | 16A AC250V (Volts free output) |
| Допоміжний релейний вихід 1 | 7A AC250V (Volts free output) |
| Допоміжний релейний вихід 2 | 7A AC250V (Volts free output) |
| Допоміжний релейний вихід 3 | 16A AC250V (Volts free output) |
| Допоміжний релейний вихід 4 | 16A AC250V (Volts free output) |
| Цифровий вхід | GND connect is active |
| спілкування | Інтерфейс LINK, протокол MODBUS |
| Розміри корпусу | 139 мм x 120 мм x 48 мм (5.47 x 4.72 x 1.89 дюйми) |
| Виріз на панелі | 130 мм х 111 мм |
| Умови праці | Температура: (-25~+70)°C, Вологість: (20~93)% відносної вологості |
| Умови зберігання | Температура: (-25~+70)°C |
| Рівень захисту | Ущільнювач IP55 |
| Міцність ізоляції | Застосувати AC2.2kV voltage між високою обtage термінал і низька гучністьtagе термінал; Струм витоку не більше 3 мА протягом 1 хв. |
| вага | 0.62 кг (1.63 фунтів) |





