This manual provides essential information for the proper installation, operation, and maintenance of the Simplex 4098-9733 Heat Detector. Adherence to these instructions is crucial for ensuring the detector's optimal performance and compliance with safety standards.

1.1 Призначення цього посібника

The purpose of this document is to guide qualified personnel through the necessary steps for deploying and managing the Simplex 4098-9733 Heat Detector within a fire alarm system. It covers technical specifications, installation procedures, operational guidelines, and maintenance recommendations.

1.2 Важлива інформація про безпеку

Завжди дотримуйтесь наступних заходів безпеки:

2. Продукт закінчивсяview

The Simplex 4098-9733 is a fixed-temperature heat detector designed to provide reliable fire detection by responding to a specific temperature threshold. It is typically integrated into a larger fire alarm system.

2.1 Основні характеристики

2.2 Компоненти продукту

The Simplex 4098-9733 Heat Detector consists of the main detector head and typically requires a compatible mounting base (sold separately) for installation into a fire alarm circuit.

A box filled with multiple red Simplex 4098-9733 heat detectors, each individually packaged in clear plastic.

This image displays a cardboard box containing numerous Simplex 4098-9733 heat detectors. Each detector is red, circular, and encased in clear plastic packaging, indicating new, unused units ready for installation.

3. Налаштування та встановлення

3.1 Перед установкою

3.2 Монтаж детектора

The 4098-9733 detector requires a compatible mounting base (e.g., Simplex 4098-9792, 4098-9789, or similar, sold separately) for proper installation.

  1. Turn off all power to the fire alarm control panel and associated circuits.
  2. Mount the detector base securely to a standard electrical box or directly to the ceiling/wall according to local codes.
  3. Connect the wiring from the fire alarm control panel to the appropriate terminals on the detector base (refer to the wiring diagram below).
  4. Align the detector head with the mounting base and rotate clockwise until it locks into place.
  5. Restore power to the fire alarm control panel and test the detector.

3.3 Електропроводка

Proper wiring is critical for the detector's functionality. Refer to the specific wiring diagram provided with your detector base and fire alarm control panel documentation. A typical wiring configuration for a two-wire system is as follows:

Typical Wiring Connections (Consult Base Manual for Specifics)
Терміналопис
1Signal Line In (+)
2Signal Line Out (+)
3Signal Line In/Out (-)
4Remote Annunciator (if applicable)

4. Інструкція з експлуатації

4.1 Нормальна робота

Under normal conditions, the Simplex 4098-9733 Heat Detector continuously monitors the ambient temperature. It draws minimal current from the fire alarm control panel and typically has an indicator LED that may flash periodically to confirm normal operation (check your specific base and panel documentation for LED behavior).

4.2 Alarm Condition

When the ambient temperature at the detector reaches or exceeds 135°F (57°C), the detector will activate. This activation sends a signal to the fire alarm control panel, initiating the alarm sequence (e.g., sounding alarms, notifying monitoring stations). The detector's LED will typically illuminate steadily to indicate its alarm state.

Upon an alarm, follow your facility's emergency procedures immediately. Do not attempt to reset the detector until the cause of the alarm has been identified and resolved.

5. Технічне обслуговування

Regular maintenance is essential to ensure the continued reliability and proper functioning of your heat detector.

5.1 Регулярна перевірка

5.2 Очищення

If dust or debris is visible, clean the exterior of the detector using a soft, dry cloth. Do not use cleaning sprays or solvents directly on the detector. For more thorough cleaning, consult a qualified fire alarm technician.

5.3 Тестування

Heat detectors should be tested periodically by qualified personnel in accordance with NFPA 72 and local fire codes. Testing typically involves applying a controlled heat source to the detector to verify its activation at the rated temperature. Never use an open flame for testing.

6. Вирішення проблем

This section addresses common issues that may arise with the Simplex 4098-9733 Heat Detector. For complex problems, contact a qualified fire alarm technician.

проблемаМожлива причинаРішення
Detector not responding to heat testIncorrect wiring, faulty detector, insufficient heat applied, incompatible base.Verify wiring connections. Ensure adequate heat is applied during testing. Check detector compatibility with base and panel. Replace detector if faulty.
Неправдиві тривогиDetector located near heat source (e.g., furnace, oven), environmental factors.Relocate detector away from heat sources. Ensure proper ventilation. Consult installation guidelines for appropriate placement.
System trouble signalWiring fault, detector not seated correctly, power issue.Check all wiring connections. Ensure detector is securely twisted onto its base. Verify power supply to the fire alarm control panel.

7. Технічні характеристики

The following table outlines the technical specifications for the Simplex 4098-9733 Heat Detector:

СпецифікаціяДеталь
Номер моделі4098-9733
Тип датчикаFixed Temperature Heat Detector
Температура активації135°F (57°C)
Тип тривогиAudible (via control panel)
Робоча вологістьДо 90% без конденсації
Джерело живленняPowered by Fire Alarm Control Panel (not battery operated)
матеріалМетал, пластик
КолірЧервоний, Білий
Вага товару3.2 унцій (приблизно)
Розміри продукту5 x 5 x 3 дюймів (прибл.)
UPC643485652892

8. Гарантія та підтримка

8.1 Інформація про гарантію

Simplex products are manufactured to high-quality standards. For specific warranty terms and conditions, please refer to the official warranty statement provided with your purchase or contact Simplex customer service. Keep your proof of purchase for warranty claims.

8.2 Технічна підтримка

For technical assistance, troubleshooting beyond this manual, or to inquire about service, please contact your authorized Simplex distributor or a qualified fire alarm service provider. Ensure you have the model number (4098-9733) and any relevant system information available when seeking support.

Пов'язані документи - 4098-9733

попередньоview Simplex TrueAlarm Analog Sensors: Photoelectric and Heat Datasheet
Comprehensive datasheet for Simplex TrueAlarm Analog Sensors, detailing photoelectric and heat models, standard bases, and accessories. Includes features, intelligent data evaluation, sensor specifications, mounting references, and product selection charts for fire alarm systems.
попередньоview Керівництво з підключення адресного променевого сповіщувача Simplex 4098-9019 IDNet та програмування FACP
Вичерпний посібник з підключення та програмування адресної системи променевих сповіщувачів Simplex 4098-9019 IDNet з панелями керування пожежною сигналізацією Simplex (FACP). Охоплює сумісність, електричні характеристики, адресацію та роботу панелі.
попередньоview Simplex 4098 Detectors, Sensors, and Bases Application Manual
This application manual provides comprehensive information on the proper use and installation of Simplex 4098 series detectors, sensors, and bases within fire alarm systems. It covers principles of operation, placement guidelines, compatibility, testing procedures, and troubleshooting for these critical fire safety components.
попередньоview Simplex 4008/4006-9801 Expansion Power Supply (EPS) Installation Guide
Installation instructions for the Simplex 4008/4006-9801 Expansion Power Supply (EPS), detailing mounting, panel interconnections, NAC wiring, auxiliary power, and NAC ratings for fire alarm systems.
попередньоview Simplex 2098 Series Smoke Detectors: Installation Instructions and Specifications
This document provides installation instructions, technical specifications, and wiring diagrams for Simplex 2098-9201, 2098-9202, 2098-9203, 2098-9208, and 2098-9576 smoke detectors, covering both photoelectric and ionization types. It details general information, special considerations for installation, applications, maintenance, testing procedures, and limitations of smoke detection technology.
попередньоview Пожежна сигналізація Simplex 4010: Керівництво з встановлення, експлуатації та програмування
Вичерпний посібник з встановлення, експлуатації та програмування системи пожежної сигналізації Simplex 4010. Охоплює систему понадview, підключення, налаштування, діагностика та усунення несправностей.