DIHOOL DHM1B-2P-200A

DIHOOL DHM1B-2P-200A DC Circuit Breaker Instruction Manual

1. Вступ

This manual provides essential information for the safe and effective use of the DIHOOL DHM1B-2P-200A DC Molded Case Circuit Breaker (MCCB). This device is designed for high current battery protection in various DC applications, including electric vehicles, Uninterruptible Power Supplies (UPS), inverters, and photovoltaic combiner boxes. Please read these instructions carefully before installation and operation.

2. Технічні характеристики

The DIHOOL DHM1B-2P-200A circuit breaker features the following technical specifications:

СпецифікаціяЗначення
МодельDHM1B-2P-200A
Номінальний робочий об'ємtageDC 12-400V
поляки2P
Номінальний струм200А
Breaking Capacity (Ics)15 кА
Breaking Capacity (Icu)25 кА
Використати категоріюA
Механічне життя6,000 разів
Електричне життя1,000 разів
Спосіб встановленняPanel screw installation
Відповідність стандартамIEC60947-2 / GB14048.2
Робоча температуравід -10 ℃ до +50 ℃
Робоча висота2000 метр
Розміри продукту (Д x Ш x В)6.9 Г x 6.5 Ш x 15 В см
Вага товару1.52 кілограма
Включені компонентиТермінал

3. Налаштування та встановлення

The DIHOOL DHM1B-2P-200A circuit breaker is designed for panel screw installation. Ensure the installation location is dry, well-ventilated, and within the specified operating temperature range.

3.1 Фізичні розміри

Understanding the physical dimensions is crucial for proper panel integration.

Diagram showing the dimensions of the DIHOOL DHM1B-2P-200A circuit breaker, with a width of 74mm and a height of 164mm.
Figure 1: Circuit breaker dimensions. The device measures 74mm in width and 164mm in height.

3.2 Підключення проводів

Proper wiring is essential for safety and performance. The circuit breaker is a 2-pole device designed to protect both positive and negative lines in a DC system.

  • Applicable Wire Diameter: The terminals are designed to accommodate wires up to 95mm² (000AWG).
  • Розміри терміналу: The conductive parts have a thickness of 5mm, and the terminal height is 85mm.
  • Полярність: For DC 12V, 24V, 36V, 48V, 96V, 120V, and 240V applications, the circuit breaker supports 'No Polarity' connection, simplifying installation.
Image showing the applicable wire diameter for the circuit breaker terminals, indicating 95mm² or 000AWG, and the thickness of conductive parts as 5mm.
Figure 2: Applicable wire diameter and conductive part thickness. The terminals accept large gauge wires.
Image detailing the terminal height of the circuit breaker, measured at 85mm.
Figure 3: Terminal height measurement, showing 85mm.
Diagram illustrating the 'No Polarity' feature for DC 12V-240V applications, showing positive and negative terminals without specific polarity requirements for connection.
Figure 4: No Polarity connection for various DC voltagес.
Wiring diagram showing a battery connected to the DIHOOL circuit breaker, which then connects to a power inverter and a light bulb, illustrating a typical DC application setup.
Малюнок 5: Впрample wiring diagram for a DC system.

4. Інструкція з експлуатації

The circuit breaker provides thermal magnetic trip functionality for circuit overload and short circuit protection.

4.1 Увімкнення/вимкнення

The circuit breaker has a clear ON/OFF handle for manual operation.

  • To Switch OFF: Натисніть на ручку ВНИЗ у положення «ВИМК.».
  • To Switch ON: Натисніть на ручку UP у положення «УВІМК.».

Примітка: If the handle is in the 'Trip OFF' state (between ON and OFF), it cannot be directly pushed UP to ON. First, perform a handle DOWN action (to fully OFF), then push the handle UP to ON to reset and engage the circuit.

4.2 Trip Function

The circuit breaker is equipped with a red 'TEST' button to manually trip the breaker for testing purposes or to isolate the circuit.

  • To Trip: Натисніть ЧЕРВОНИЙ button. This will move the handle to the 'Trip OFF' state, indicating no electricity flow.
Diagram illustrating the operating instructions for the circuit breaker, showing how to push the handle down for OFF, up for ON, and press the red button to trip.
Figure 6: Operating instructions for switching ON/OFF and tripping the circuit breaker.

4.3 Функції захисту

  • Thermal Magnetic Trip: Protects against sustained overcurrents (thermal) and sudden high currents (magnetic).
  • Circuit Overload Protection: Automatically trips when current exceeds the rated 200A for a prolonged period.
  • Circuit Short Circuit Protection: Instantly trips upon detection of a short circuit. Note that for voltages between 12V-30V, short circuit protection is not active; it is active for 32V-400V.
  • Isolation Circuit: Provides a safe means to disconnect power for maintenance or safety.

5. Технічне обслуговування

To ensure the longevity and reliable operation of your DIHOOL DHM1B-2P-200A circuit breaker, follow these general maintenance guidelines:

  • Регулярна перевірка: Періодично перевіряйте автоматичний вимикач на наявність будь-яких ознак фізичних пошкоджень, зміни кольору або нещільних з'єднань.
  • Прибирання: Keep the circuit breaker free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners or solvents.
  • Перевірка терміналу: Ensure all terminal connections are tight and secure. Loose connections can lead to overheating and potential hazards.
  • Функція перевірки: Periodically use the red 'TEST' button to verify the tripping mechanism is functional.

Always disconnect power to the circuit before performing any inspection or maintenance.

6. Вирішення проблем

If you encounter issues with your DIHOOL DHM1B-2P-200A circuit breaker, consider the following troubleshooting steps:

  • Часті спрацьовування автоматичного вимикача:
    • Check for overloads: Ensure the connected load does not exceed the 200A rated current.
    • Check for short circuits: Inspect wiring for any signs of damage or short circuits.
    • Перевірити випtage: Ensure the operating voltage is within the DC 12-400V range.
  • Breaker Does Not Trip:
    • Manually test the trip function using the red 'TEST' button. If it does not trip, the unit may be faulty.
    • Ensure the current is sufficient to cause a trip for the detected fault (e.g., short circuit protection is not active below 32V).
  • Breaker Does Not Stay ON:
    • If the handle is in the 'Trip OFF' state, push it fully DOWN to OFF before attempting to push it UP to ON.
    • If the breaker immediately trips after being switched ON, a persistent overload or short circuit is present.

If problems persist after performing these checks, consult a qualified electrician or contact DIHOOL customer support.

7. Гарантія та підтримка

For information regarding the warranty period and terms for your DIHOOL DHM1B-2P-200A DC Circuit Breaker, please refer to the documentation provided at the time of purchase or contact your retailer. For technical support or further assistance, please reach out to DIHOOL customer service through their official channels.