The Robertshaw uni-line 712 series pilot ignition system features flame rectification with solid-state logic and flame sensing. This system provides automatic sequencing to ensure proper operation of an intermittent pilot ignition device. The 712 series pilot ignition system is designed for quick and easy installation, and includes comprehensive instructions and troubleshooting information. These systems are available with various gas valve types to suit a wide range of furnace applications, handling up to 720,000 BTU (natural gas) depending on the model. The SP845 lockout ignition control, used in the 712 lockout uni-kits, provides 90 seconds of spark followed by a six-minute time delay (purge) period between ignition attempts. After three unsuccessful tries, if no pilot flame is sensed, the SP845 enters a 1-hour lockout period. If the demand for heat persists after this lockout, the unit will automatically repeat the three ignition attempts.

Ключові характеристики

  • Converts conventional standing pilot systems to intermittent pilot systems.
  • Suitable for use with residential and commercial heating equipment.
  • Includes 720-070 valve, 780-715 module, wiring harness, spark/sensor probe, and mounting hardware.
  • Inlet/outlet dimensions: 1/2 x 3/4 inches.
  • BTU capacity: 200,000 NG (Natural Gas).
Robertshaw 712-017 Pilot Ignitor System components

малюнок 1: закінченоview of the Robertshaw 712-017 Pilot Ignitor System components, including the valve, module, and wiring.

2. Інформація про безпеку

УВАГА: Неправильне встановлення, регулювання, зміни, обслуговування або технічне обслуговування може призвести до пошкодження майна, травм або смерті. Перед установкою або обслуговуванням цього обладнання уважно прочитайте інструкції з встановлення, експлуатації та технічного обслуговування.

  • Always disconnect electrical power and shut off the gas supply to the appliance before performing any service.
  • Встановлення та обслуговування повинні виконуватися кваліфікованим установником, сервісним агентством або постачальником газу.
  • Переконайтеся, що всі електропроводкові з'єднання відповідають місцевим та національним електротехнічним нормам.
  • Check for gas leaks after installation or service using a soap solution; never use an open flame.
  • Не зберігайте та не використовуйте бензин або інші легкозаймисті пари та рідини поблизу цього чи будь-якого іншого приладу.
  • This product is designed for natural gas (NG) applications. Refer to product specifications for compatibility with other gas types.

3. Вміст упаковки

Перед початком встановлення перевірте наявність усіх компонентів:

  • Газовий клапан Robertshaw 720-070
  • Robertshaw 780-715 Ignition Module
  • Джгут
  • Spark/Sensor Probe Assembly
  • Монтажне обладнання
  • Інструкції з монтажу та експлуатації

4. Монтаж

Installation of the Robertshaw 712-017 Pilot Ignitor System should be performed by a qualified service technician. Refer to the detailed installation instructions provided with the product for specific wiring diagrams and mounting procedures.

  1. Приготування: Disconnect all electrical power to the appliance and shut off the main gas supply.
  2. Remove Old System: Carefully remove the existing pilot system and associated components, if applicable.
  3. Компоненти кріплення: Mount the new 720-070 gas valve and 780-715 ignition module in appropriate locations, ensuring proper ventilation and access for service.
  4. Підключення газових труб: Connect the gas piping to the new valve, ensuring all connections are tight and leak-free.
  5. Дротові з'єднання: Connect the wiring harness to the ignition module, spark/sensor probe, and appliance controls according to the provided wiring diagram. Ensure all electrical connections are secure.
  6. Тест на герметичність: Restore gas supply and perform a thorough leak test on all gas connections using a non-corrosive soap solution.
  7. Electrical Test: Restore electrical power and test the system operation as described in the operating instructions.

Важливо: Always verify proper operation and safety controls after installation.

5. Інструкція з експлуатації

The Robertshaw 712-017 Pilot Ignitor System operates automatically in response to a call for heat from the thermostat.

  1. Виклик опалення: When the thermostat calls for heat, the ignition module initiates a sequence.
  2. Spark Ignition: The module sends a spark to the pilot burner, attempting to ignite the pilot flame.
  3. Датчик полум'я: Once the pilot flame is established, the flame sensor detects its presence, signaling the module.
  4. Запалювання основного пальника: Upon successful pilot ignition, the main gas valve opens, allowing gas to flow to the main burners, which are then ignited by the pilot flame.
  5. Heat Cycle Completion: The system continues to operate until the thermostat's call for heat is satisfied, at which point the main burner and pilot flame are extinguished.

Lockout Feature (SP845 Control)

  • The SP845 lockout ignition control provides 90 seconds of spark during each ignition attempt.
  • If ignition is not achieved, there is a six-minute time delay (purge) before the next attempt.
  • After three unsuccessful ignition attempts, the SP845 enters a 1-hour lockout period.
  • If the demand for heat is still present after the 1-hour lockout, the unit will automatically repeat the three ignition attempts.

6. Технічне обслуговування

Regular maintenance ensures the longevity and efficient operation of your Robertshaw 712-017 Pilot Ignitor System. All maintenance should be performed by a qualified service technician.

  • Щорічна перевірка: Have the entire heating system, including the pilot ignitor, inspected annually by a qualified technician.
  • Чистота: Ensure the pilot burner and flame sensor are free from dust, lint, and debris. A dirty sensor can prevent proper flame detection.
  • Перевірка проводки: Періодично перевіряйте всі з'єднання проводів на міцність та наявність ознак зносу або пошкоджень.
  • Тиск газу: Verify that the gas pressure to the valve is within the manufacturer's specified range.
  • Цілісність компонентів: Inspect the gas valve and ignition module for any visible signs of damage or corrosion.

7. Вирішення проблем

Before attempting any troubleshooting, ensure all safety precautions are followed, including disconnecting power and gas supply. If you are not a qualified technician, contact a professional for assistance.

проблемаМожлива причинаРішення
No ignition/Pilot not lightingNo power to the module, no gas supply, faulty spark/sensor probe, dirty pilot burner, module in lockout.Check power supply, verify gas valve is open, inspect and clean pilot assembly, check for module lockout (wait 1 hour or reset power if applicable), test spark/sensor probe.
Main burner does not ignite after pilot lightsWeak pilot flame, faulty flame sensor, main gas valve issue.Adjust pilot flame, clean or replace flame sensor, check main gas valve operation.
System goes into lockout frequentlyIntermittent pilot ignition failure, low gas pressure, faulty module.Inspect pilot assembly for obstructions, verify gas pressure, test or replace ignition module.

For detailed troubleshooting steps and diagnostic procedures, refer to the complete manual provided with your system or consult a qualified HVAC technician.

8. Технічні характеристики

ОсобливістьДеталь
Номер моделі712-017
ВиробникСтандартне сантехнічне постачання
Вага товару3 фунта
Розміри продукту3 x 3 x 4.13 дюймів
Включені компоненти720-070 Valve, 780-715 Module, Wiring Harness, Spark/Sensor Probe, Mounting Hardware
Inlet/Outlet (Gas Valve)1/2 x 3/4 дюймів
BTU Capacity (Natural Gas)200,000 BTU
Тип запалюванняПереривчастий пілот
Lockout ControlSP845 (90 sec spark, 6 min purge, 3 tries, 1 hr lockout)

9. Гарантія та підтримка

Robertshaw products are manufactured to high-quality standards. For specific warranty information, please refer to the documentation included with your purchase or visit the official Robertshaw webсайт.

For technical support, service, or replacement parts, please contact a qualified HVAC professional or Robertshaw customer service directly. When contacting support, please have your model number (712-017) and purchase date available.

Робертшоу Webсайт: www.robertshaw.com

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.